Technical Data
10-42
7SA6 Manual
C53000-G1176-C156
10.19 Monitoring Functions
Measured Values
Current sum
I
F
= |
I
L1
+
I
L2
+
I
L3
+ k
I
·
I
E
|>
SUM.I Threshold · I
N
+ SUM.I factor· I
max
– SUM.I Threshold
0.05 A to 2.00 A
(steps 0.01)
– SUM.I factor
0.00 to 0.95
(steps 0.01)
Voltage sum
U
F
= |U
L1
+ U
L2
+ U
L3
+ k
U
U
EN
| > 25 V
Current symmetry
|
I
min
| / |
I
max
| < BAL.FACTOR I
as long as
I
max
/
I
N
> BAL.I LIMIT /
I
N
– BAL.FACTOR I
0.10 to 0.95
(steps 0.01)
– BAL.I LIMIT
0.10 A to 1.00 A
(steps 0.01 A)
Broken conductor
one conductor without current,
the others with current
Voltage symmetry
|U
min
| / |U
max
| < BAL.FACTOR U
as long as |Umax| > BAL.U LIMIT
– BAL.FACTOR U
0.58 to 0.95
(steps 0.01)
– BAL.U LIMIT
10 V to 100 V
(steps 1 V)
Voltage phase rotation
U
L1
before U
L2
before U
L3
as long as |U
L1
|, |U
L2
|, |U
L3
| > 40 V/
√
3
Fuse–Failure–Monitor
3·U
0
> FFM U> OR 3·U
2
> FFM U>
(non-symmetrical voltages)
AND
at the same time
3·I
0
< FFM I< AND 3·I
2
< FFM I<
– FFM U>
10 V to 100 V
(steps 0.01 V)
– FFM I<
0.10·A to 1.00·A
1)
(steps 0.01·A)
Fuse–Failure–Monitor
all U
Ph-E
< FFM U<max
(three-phase)
AND
at the same time
all
∆
I
Ph
< FFM Idelta
AND
all I
Ph
> (I
Ph
> (Dist.))
OR
all U
Ph-E
< FFM U<max
AND
at the same time
all I
Ph
< (I
Ph
> (Dist.))
AND
all I
Ph
> 40 mA
– FFM U<max
2 V to 100 V
(steps 1 V)
– FFM I
delta
0.05·A to 1.00·A
1)
(steps 0.01·A)
1
) Secondary values based on I
N
= 1 A; for I
N
= 5 A they must be multiplied by 5.
Trip Circuit
Supervision
Number of monitored circuits
1 to 3
Operation
with 1 binary input or with 2 binary inputs
Alarm delay
1 s to 30 s
(steps 1 s)
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...