Figure 6-33
Release logic for a zone (example for Z1)
In total the following zones are available:
Independent zones:
•
1st zone (fast tripping zone) Z1 with
R(Z1)
,
X(Z1)
; may be delayed by
T1-
1phase
and
T1-multi-phase
•
2nd zone (back up zone) Z2 with
R(Z2)
,
X(Z2)
; may be delayed by
T2-1phase
and
T2-multi-phase
•
3rd zone (back up zone) Z3 with
R(Z3)
,
X(Z3)
; may be delayed by
T3 DELAY
•
4th zone (back up zone) Z4 with
R(Z4)
,
X(Z4)
; may be delayed by
T4 DELAY
•
5th zone (back up zone) Z5 with
R(Z5)
,
X(Z5)+
(forward) and X (Z5)-
(reverse); may be delayed by
T5 DELAY
Dependent (controlled) zone:
•
Overreaching zone Z1B with
R(Z1B)
,
X(Z1B)
; may be delayed by
T1B-1phase
and
T1B-multi-phase
6.2.4.2
Applying the Function Parameter Settings
Grading
Coordination Chart
It is recommended to initially create a grading coordination chart for the entire galvan-
ically interconnected system. This diagram should reflect the line lengths with their pri-
mary reactance X in
Ω
/phase. For the reach of the distance zones, the reactances X
are the deciding quantities.
The first zone Z1 is usually set to cover 85 % of the protected line without any trip time
delay (i.e. T1 = 0.00 s). The protection clears faults in this range without additional
time delay, i.e. the tripping time is the relay basic operating time.
The tripping time of the higher zones is sequentially increased by one time grading
margin. The grading margin must take into account the circuit breaker operating time
including the spread of this time, the resetting time of the protection equipment as well
as the spread of the protection delay timers. Typical values are 0.2 s to 0.4 s. The
reach is selected to cover up to approximately 80 % of the zone with the same set time
delay on the shortest neighbouring feeder.
Dis switched off
Dis blocked
≥
1
PS blocking
reverse
forward
non-directional
inactive
Dis FD forward
Dis FD reverse
&
&
≥
1
&
Op. mode Z1
„1“
&
further
zones
release of Z1
1301
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...