Appendix
B-15
7SA6 Manual
C53000-G1176-C156-2
3173
SOTF Time DELAY Earth fault overcur-
rent
0.00..30.00 sec
0.00 sec
Trip time delay after SOTF
3182
3U0>(U0 inv)
Earth fault overcur-
rent
1.0..10.0 V
5.0 V
3U0> setpoint
3183
U0inv. minimum
Earth fault overcur-
rent
0.1..5.0 V
0.2 V
Minimum voltage U0min for T->oo
3184
T forw. (U0inv)
Earth fault overcur-
rent
0.00..32.00 sec
0.90 sec
T-forward Time delay (U0inv)
3185
T rev. (U0inv)
Earth fault overcur-
rent
0.00..32.00 sec
1.20 sec
T-reverse Time delay (U0inv)
3201
FCT Telep. E/F
Teleprotection for
Earth fault overcurr.
ON
OFF
ON
Teleprotection for Earth Fault O/C
3202
Line Config.
Teleprotection for
Earth fault overcurr.
Two Terminals
Three Terminals
Two Terminals
Line Configuration
3203A
Send Prolong.
Teleprotection for
Earth fault overcurr.
0.00..30.00 sec
0.05 sec
Time for send signal prolongation
3207A
Delay for alarm
Teleprotection for
Earth fault overcurr.
0.00..30.00 sec
10.00 sec
Unblocking: Time Delay for Alarm
3208
Release Delay
Teleprotection for
Earth fault overcurr.
0.000..30.000 sec
0.000 sec
Time Delay for release after pickup
3209A
TrBlk Wait Time
Teleprotection for
Earth fault overcurr.
0.00..30.00 sec;
∞
0.04 sec
Transient Block.: Duration external flt.
3210A
TrBlk BlockTime
Teleprotection for
Earth fault overcurr.
0.00..30.00 sec
0.05 sec
Transient Block.: Blk.T. after ext. flt.
3401
AUTO RECLOSE
Automatic Reclo-
sure
OFF
ON
ON
Auto-Reclose function
3402
CB? 1.TRIP
Automatic Reclo-
sure
YES
NO
NO
CB ready interrogation at 1st trip
3403
T-RECLAIM
Automatic Reclo-
sure
0.50..300.00 sec
3.00 sec
Reclaim time after successful AR cycle
3404
T-BLOCK MC
Automatic Reclo-
sure
0.50..300.00 sec; 0
1.00 sec
AR blocking duration after manual
close
3406
EV. FLT. RECOG.
Automatic Reclo-
sure
with Pickup
with Trip
with Trip
Evolving fault recognition
3407
EV. FLT. MODE
Automatic Reclo-
sure
blocks AR
starts 3pole AR-cycle
starts 3pole AR-cycle
Evolving fault (during the dead time)
3408
T-Start MONITOR
Automatic Reclo-
sure
0.01..300.00 sec
0.20 sec
AR start-signal monitoring time
3409
CB TIME OUT
Automatic Reclo-
sure
0.01..300.00 sec
3.00 sec
Circuit Breaker (CB) Supervision Time
3410
T RemoteClose
Automatic Reclo-
sure
0.00..300.00 sec;
∞
∞
sec
Send delay for remote close command
3411A
T-DEAD EXT.
Automatic Reclo-
sure
0.50..300.00 sec;
∞
∞
sec
Maximum dead time extension
3420
AR w/ DIST.
Automatic Reclo-
sure
YES
NO
YES
AR with distance protection
3421
AR w/ SOTF-O/C
Automatic Reclo-
sure
YES
NO
YES
AR with switch-onto-fault overcurrent
3422
AR w/ W/I
Automatic Reclo-
sure
YES
NO
YES
AR with weak infeed tripping
3423
AR w/ EF-O/C
Automatic Reclo-
sure
YES
NO
YES
AR with earth fault overcurrent prot.
3424
AR w/ DTT
Automatic Reclo-
sure
YES
NO
YES
AR with direct transfer trip
3425
AR w/ BackUpO/C
Automatic Reclo-
sure
YES
NO
YES
AR with back-up overcurrent
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...