Control During Operation
7-9
7SA6 Manual
C53000-G1176-C156-2
Figure 7-9
Example of fault messages in DIGSI
®
4
7.1.1.4
Earth Fault Messages
Devices with sensitive earth fault detection provide special earth fault logs. The earth
faults are registered if the earth fault detection function is set to “OFF” (Address
3001
=
Alarm Only
) and an earth fault was already in queue so that the trip delay (
T
Sens.E/F
) could expire.
Up to 200 earth fault messages can be stored for the last 8 earth faults.
All available indications are displayed and explained in Appendix B. In a specific case,
of course, only the applicable messages appear on the display.
From the
DeviceFront
With a device ready for operation, first press the
key. The
MAIN MENU
appears.
The first menu item (
Annunciation
) is marked.
Press the
key to enter the
ANNUNCIATION
sub-menu (see Figure 7-1).
Using the
key, select the sub-menu item
Earth Fault Messages
and move to
the earth fault logs using the
key. The
EARTH FAULT MESSAGES
selection ap-
pears.
In this sub-menu, the indications for the last 3 network faults can be selected, again
using the
and
keys. See the example in Figure 7-10.
If no messages are present for a fault, then entrance is denied and “
List Empty
” is
displayed.
The messages within an earth fault log are listed in chronological order and numbered
consecutively, from the oldest to the newest ones.
The inception of an earth fault is identified with the date (without indication of the year)
and time in hours, minutes, and seconds (resolution = 1 ms). See the example in Fig-
ure 7-10.
MENU
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...