Configuration
5-13
7SA6 Manual
C53000-G1176-C156-2
Figure 5-8
Double command with double contacts (with 4 relays)
Figure 5-9
Double command with double and single contacts (with 3 relays)
For the motor control illustrated in Figure 5-10 the following can be realized:
−
via CLOSE command
anti-clockwise rotation
−
via TRIP command
clockwise rotation
−
and in quiescient state
TRIP
The power relays with 2 NO contacts (each) to be used for this purpose are interlocked
against eachother so that only one relay can be connected.
When using the power relay for a motor controlled three-position disconnector
please observe the following:
For the disconnector and earth switch function the same output relays are controlled
by two different commands. Since both end positions are achieved by different rotation
of the motor, one of the two commands must be negated. Therefore the command
types e. g.
CF_D2
and
CF_D2N
are to be applied in this case.
CLOSE
Command
C+1
C+2
TRIP
Command
C–1
t
CLOSE
TRIP
Switching
C+1
C–1
L+
L–
C+2
C–2
C–2
Matrix Configuration:
C+1
X
1
C–
1
X
2
3
4
C+2
X
C–
2
X
Device
CLOSE
Command
C+1
C+2
TRIP
Command
C–
t
CLOSE
TRIP
Switching
Device
C+1
C–
L+
L–
C+2
Matrix Configuration:
C+1
X
1
C–
X
2
3
X
C+2
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...