Appendix
B-33
7SA6 Manual
C53000-G1176-C156-2
1397
EF Tele.Carrier RECEPTION, L1, Device3
(EF Rec.L1 Dev3)
Teleprotection for
Earth fault over-
curr.
OUT
on
off
on
LED
BO
1398
EF Tele.Carrier RECEPTION, L2, Device3
(EF Rec.L2 Dev3)
Teleprotection for
Earth fault over-
curr.
OUT
on
off
on
LED
BO
1399
EF Tele.Carrier RECEPTION, L3, Device3
(EF Rec.L3 Dev3)
Teleprotection for
Earth fault over-
curr.
OUT
on
off
on
LED
BO
1401
>BF: Switch on breaker fail protection
(>BF on)
Breaker Failure
SP
*
*
LED BI
BO
1402
>BF: Switch off breaker fail protection
(>BF off)
Breaker Failure
SP
*
*
LED BI
BO
1403
>BLOCK Breaker failure (>BLOCK Bkr-
Fail)
Breaker Failure
SP
ON
OFF
*
LED BI
BO
166 103 1
GI
1415
>BF: External start 3pole (>BF Start 3pole) Breaker Failure
SP
ON
OFF
*
LED BI
BO
1432
>BF: External release (>BF release)
Breaker Failure
SP
ON
OFF
*
LED BI
BO
1435
>BF: External start L1 (>BF Start L1)
Breaker Failure
SP
ON
OFF
*
LED BI
BO
1436
>BF: External start L2 (>BF Start L2)
Breaker Failure
SP
ON
OFF
*
LED BI
BO
1437
>BF: External start L3 (>BF Start L3)
Breaker Failure
SP
ON
OFF
*
LED BI
BO
1439
>BF: External start 3pole (w/o current)
(>BF Start w/o I)
Breaker Failure
SP
ON
OFF
*
LED BI
BO
1440
Breaker failure prot. ON/OFF via BI (Bkr-
FailON/offBI)
Breaker Failure
IntSP
ON
OFF
*
LED
BO
1451
Breaker failure is switched OFF (BkrFail
OFF)
Breaker Failure
OUT
ON
OFF
*
LED
BO
166 151 1
GI
1452
Breaker failure is BLOCKED (BkrFail
BLOCK)
Breaker Failure
OUT
ON
OFF
ON
OFF
LED
BO
166 152 1
GI
1453
Breaker failure is ACTIVE (BkrFail
ACTIVE)
Breaker Failure
OUT
*
*
LED
BO
166 153 1
GI
1461
Breaker failure protection started (BF
Start)
Breaker Failure
OUT
*
ON
OFF
LED
BO
166 161 1
GI
1472
BF Trip T1 (local trip) - only phase L1 (BF
T1-TRIP 1pL1)
Breaker Failure
OUT
*
ON
LED
BO
1473
BF Trip T1 (local trip) - only phase L2 (BF
T1-TRIP 1pL2)
Breaker Failure
OUT
*
ON
LED
BO
1474
BF Trip T1 (local trip) - only phase L3 (BF
T1-TRIP 1pL3)
Breaker Failure
OUT
*
ON
LED
BO
1476
BF Trip T1 (local trip) - 3pole (BF T1-TRIP
L123)
Breaker Failure
OUT
*
ON
LED
BO
1493
BF Trip in case of defective CB (BF TRIP
CBdefec)
Breaker Failure
OUT
*
ON
LED
BO
1494
BF Trip T2 (busbar trip) (BF T2-TRIP(bus)) Breaker Failure
OUT
*
ON
LED
BO
128 85
2
1495
BF Trip End fault stage (BF EndFlt TRIP)
Breaker Failure
OUT
*
ON
LED
BO
F.No.
Description
Function
Type of
Informa-
tion
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
E
v
en
t
L
o
g
On
/O
ff
T
rip
(F
au
lt)
L
o
g
On
/Of
f
G
roun
d
F
a
u
lt
Lo
g
O
n
/O
ff
M
a
rk
e
d
in
Osc
ill.
Reco
rd
LED
B
ina
ry
In
pu
t
Fun
ct
io
n
K
e
y
B
ina
ry
O
u
tp
ut
C
h
at
te
r
B
lo
c
k
in
g
Ty
pe
In
fo
rm
a
tio
n
-N
o
D
a
ta
Un
it
(A
SDU)
G
e
ne
ra
l
In
te
rr
oga
ti
o
n
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...