Control During Operation
7-43
7SA6 Manual
C53000-G1176-C156-2
The following diagram shows the test sequence in principal:
Figure 7-43
TRIP-CLOSE test cycle
The initiation of the test is done via the keypad and display on the front of the device
or with a PC running DIGSI
®
4. Entry of the password (password No. 4 for test and
diagnostics) is required.
From the
DeviceFront
With the device ready for operation, first press the
key. The
MAIN MENU
appears.
Select the
Test/Diagnose
option using the
key and enter the sub-menu
TEST/
DIAGNOSE
with the
key.
With the
key, the
CB test
(21) is now marked and the test program is selected
with the
key.
A prompt for entry of password No. 4 (test and diagnostics) appears. After entry of the
password and confirmation with
, the query “
Breaker closed?
” appears, with
the default response “Yes” (Figure 7-44). This must be confirmed by pressing the
key if the circuit breaker is definitely closed.
If circuit breaker auxiliary contacts are connected and marshalled, the device rejects
the test cycle when the auxiliary contacts indicate that the circuit breaker is not closed,
CB-TEST running
Circuit breaker test in progress
CB-TSTstop FLT.
Circuit breaker test cannot be started as a system fault is
present
CB-TSTstop OPEN
Circuit breaker test cannot be started as the circuit breaker
is not closed
CB-TSTstop NOTr
Circuit breaker test cannot be started as the circuit breaker
is not ready
CB-TSTstop CLOS
Circuit breaker test has been terminated as the CB is still
closed (prior to CB test reclosure)
CB-TST .OK.
Circuit breaker test cycle has been completed successfully
TRIP
CLOSE
t
T TRIP CMD.MIN.
T CLS. CMD MAX.
T PAUSE TEST
DANGER!
A successful initiation of a test cycle may cause closure of the circuit breaker if
an external reclose device is available!
MENU
ENTER
ENTER
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...