Appendix
B-9
7SA6 Manual
C53000-G1176-C156-2
1601
PROGAM U/I
Distance protec-
tion, general set-
tings
Ph-E: Uphe/ Ph-Ph: Uphph
Ph-E: Uphph/Ph-Ph: Uphph
Ph-E: Uphe/Ph-Ph: Uphe
Ph-E: Uphe/Ph-Ph: I>>
Ph-E: Uphe/ Ph-Ph: Uphph
Pickup program U/I
1602
DELAY FORW. PU Distance protec-
tion, general set-
tings
0.00..30.00 sec;
∞
1.20 sec
Trip delay for Forward-PIKKUP
1603
DEL. NON-DIR PU
Distance protec-
tion, general set-
tings
0.00..30.00 sec;
∞
1.20 sec
Trip delay for non-directional PICKUP
1610
Iph>>
Distance protec-
tion, general set-
tings
0.25..10.00 A
1.80 A
Iph>> Pickup (overcurrent)
1611
Iph>
Distance protec-
tion, general set-
tings
0.10..4.00 A
0.20 A
Iph> Pickup (minimum current)
1612
Uph-e (I>>)
Distance protec-
tion, general set-
tings
20..70 V
48 V
Undervoltage (ph-e) at Iph>>
1613
Uph-e (I>)
Distance protec-
tion, general set-
tings
20..70 V
48 V
Undervoltage (ph-e) at Iph>
1614
Uph-ph (I>>)
Distance protec-
tion, general set-
tings
40..130 V
80 V
Undervoltage (ph-ph) at Iph>>
1615
Uph-ph (I>)
Distance protec-
tion, general set-
tings
40..130 V
80 V
Undervoltage (ph-ph) at Iph>
1616
Iphi>
Distance protec-
tion, general set-
tings
0.10..8.00 A
0.50 A
Iphi> Pickup (minimum current at phi>)
1617
Uph-e (Iphi>)
Distance protec-
tion, general set-
tings
20..70 V
48 V
Undervoltage (ph-e) at Iphi>
1618
Uph-ph (Iphi>)
Distance protec-
tion, general set-
tings
40..130 V
80 V
Undervoltage (ph-ph) at Iphi>
1619A
EFFECT
ϕ
Distance protec-
tion, general set-
tings
forward and reverse
Forward
forward and reverse
Effective direction of phi-pickup
1620
ϕ
>
Distance protec-
tion, general set-
tings
30..60
°
50
°
PHI> pickup (lower setpoint)
1621
ϕ
<
Distance protec-
tion, general set-
tings
90..120
°
110
°
PHI< pickup (upper setpoint)
1630A
1ph FAULTS
Distance protec-
tion, general set-
tings
phase-earth
phase to phase only
phase-earth
1ph-pickup loop selection (PU w/o
earth)
2002
P/S Op. mode
Power Swing
all zones blocked
Z1/Z1B blocked
Z2 to Z5 blocked
Z1,Z1B,Z2 blocked
all zones blocked
Power Swing Operating mode
2006
PowerSwing trip
Power Swing
NO
YES
NO
Power swing trip
2101
FCT Telep. Dis.
Teleprotection for
Distance prot.
ON
PUTT (Z1B acceleration)
POTT
OFF
ON
Teleprotection for Distance prot. is
2102
Type of Line
Teleprotection for
Distance prot.
Two Terminals
Three Terminals
Two Terminals
Type of Line
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...