Technical Data
10-2
7SA6 Manual
C53000-G1176-C156
10.1
General Device Data
10.1.1 Analog Inputs
Nominal frequency
f
N
50 Hz or 60 Hz(adjustable)
Current Inputs
Nominal current
I
N
1 A or 5 A
Power consumption
per phase and earth path
– at I
N
= 1 A
approx. 0.05 VA
– at I
N
= 5 A
approx. 0.3 VA
– Sensitive earth fault detection at 1 A
approx. 0.05 VA
Current overload capability per input
– thermal (rms)
500 A for 1 s
150 A for 10 s
20 A continuous
– dynamic (pulse)
1250 A (half cycle)
Current overload capability
for sensitive earth current input
– thermal (rms)
300 A for 1 s
100 A for 10 s
15 A continuous
– dynamic (pulse)
750 A (half cycle)
Voltage Inputs
Nominal voltage
U
N
80 V to 125 V (adjustable)
Power consumption per phase at 100 V
≤
0.1 VA
Overload capability per phase
– thermal (rms)
230 V continuous
Analog Output
(for Measured
Values and
Fault Location)
Range
0 to 24 mA–
– Connection for flush mounting
housing
rear panel, mounting location „B“ or/and „D“
9-pin D-subminiture female connector
for surface mounting housing
on case bottom or/and on case top
– max. load impedance
350
Ω
10.1.2 Power Supply
Direct Voltage
Voltage supply via integrated DC/DC converter:
Nominal power supply
direct voltage U
N DC
24/48 VDC
60/110/125 VDC
110/125/220/
250 VDC
Permissible voltage ranges
19 to 58 VDC
48 to 150 VDC
88 to 300 VDC
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...