Functions
6-142
7SA6 Manual
C53000-G1176-C156-2
Figure 6-79
Logic diagram of the directional comparison scheme (one line end)
For earth fault protection, only directional comparison pickup is offered for
transmission via protection interface. The directional comparison pickup scheme is
only effective if the parameter
132
Teleprot. E/F
has been set to
Direction
Comparison over Protection Interface
in all devices of the setup. In the
event of an error, the indication
Par. different
is output.
Two terminals
EF Telep. off
EF TeleprotBLK
EF Pickup
&
EF forward
3203
Send Prolong.
T
0
&
EF Enable Trip
>EF Rec.Ch1
>EF Rec.Ch2
Three terminals
Two terminals
Three terminals
„1“
3202
Line Config.
≥
1
&
Trip command
&
Transient blocking
≥
1
&
≥
1
EF Tele SEND
EF TeleprotOFF
≥
1
&
≥
1
Echo function
section 6.8.1.5
FNo 1313
FNo 1318
FNo 1319
FNo 1381
FNo 1384
Weak infeed
tripping
acc. Fig. 6-89
&
3208
Release Delay
T
0
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...