Technical Data
10-37
7SA6 Manual
C53000-G1176-C156
Pick-up time
approx. 75 ms
Drop-off time
approx. 30 ms
Tolerances
voltages
3 % of set value or 1 V
times
1 % of set value or 10 ms
Undervoltage
Phase–Earth
Undervoltage
U
Ph
<<
1.0 V to 100.0 V
(steps 0.1 V)
Time delay
T
UPh<<
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Undervoltage
U
Ph
<
1.0 V to 100.0 V
(steps 0.1 V)
Time delay
T
UPh<
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Drop-off to pick-up ratio
approx. 1.05
Current criterion
can be switched on/off
Pick-up time
approx. 30 ms
Drop-off time
approx. 30 ms
Tolerances
voltages
3 % of set value or 1 V
times
1 % of set value or 10 ms
Undervoltage
Phase–Phase
Undervoltage
U
PhPh
<<
1.0 V to 175.0 V
(steps 0.1 V)
Time delay
T
UPhPh<<
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Undervoltage
U
PhPh
<
1.0 V to 175.0 V
(steps 0.1 V)
Time delay
T
UPhPh<
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Drop-off to pick-up ratio
approx. 1.05
Current criterion
can be switched on/off
Pick-up time
approx. 30 ms
Drop-off time
approx. 30 ms
Tolerances
voltages
3 % of set value or 1 V
times
1 % of set value or 10 ms
Undervoltage
Positive Sequence
System U
1
Undervoltage
U
1
<<
1.0 V to 100.0 V
(steps 0.1 V)
Time delay
T
U1<<
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Undervoltage
U
1
<
1.0 V to 100.0 V
(steps 0.1 V)
Time delay
T
U1<
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Drop-off to pick-up ratio
approx. 1.05
Current criterion
can be switched on/off
Pick-up time
approx. 30 ms
Drop-off time
approx. 30 ms
Tolerances
voltages
3 % of set value or 1 V
times
1 % of set value or 10 ms
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...