Technical Data
10-22
7SA6 Manual
C53000-G1176-C156
Negative sequence current 3I
2
>
0.05 A to 1.00 A
1
)
(steps 0.01 A)
Negative sequence voltage 3U
2
>
0.5 V to 10.0 V
(steps 0.1 V)
“Forward” angle
capacitive
Alpha
0° to 360°
(steps 1°)
inductive
Beta
0° to 360°
(steps 1°)
Tolerances pick-up values
10 % of set value
or 5% of nominal current or 0.5 V
“Forward” angle
5°
Re-orientation time after direction change approx. 30 ms
1
) Secondary values based on I
N
= 1 A; for I
N
= 5 A they must be multiplied by 5.