be used “
>DTT Trip L1
”, “
>DTT Trip L2
” and “
>DTT Trip L3
”. Figure 6-90 there-
fore also applies in this case.
6.10.2 Applying the Function Parameter Settings
A prerequisite for the application of the direct and remote tripping functions is that dur-
ing the configuration of the scope of functions in the device (Section 5.1) the setting in
address
122
DTT Direct Trip
=
Enabled
was applied. In address
2201
DTT Di-
rect Trip
ON
or
OFF
, it is furthermore possible to switch the function on or off.
It is possible to set a trip delay for both the local external trip and the receive side of
the remote trip in address
2202
Trip Time DELAY
. This can be used as a security
time margin, especially in the case of local trip.
Once a trip command has been issued, it is maintained for at least as long as the set
minimum trip command duration
TMin TRIP CMD
, which was set for the device in
general in address 240A (Sub-section 6.1.1). Reliable operation of the circuit breaker
is therefore ensured, even if the initiating signal pulse is very short.
6.10.3 Settings
6.10.4 Information Overview
Addr.
Setting Title
Setting Options
Default Setting
Comments
2201
FCT Direct Trip
ON
OFF
OFF
Direct Transfer Trip (DTT)
2202
Trip Time DELAY
0.00..30.00 sec;
∞
0.01 sec
Trip Time Delay
F.No.
Alarm
Comments
4403
>BLOCK DTT
>BLOCK Direct Transfer Trip function
4412
>DTT Trip L1
>Direct Transfer Trip INPUT Phase L1
4413
>DTT Trip L2
>Direct Transfer Trip INPUT Phase L2
4414
>DTT Trip L3
>Direct Transfer Trip INPUT Phase L3
4417
>DTT Trip L123
>Direct Transfer Trip INPUT 3ph L123
4421
DTT OFF
Direct Transfer Trip is switched OFF
4422
DTT BLOCK
Direct Transfer Trip is BLOCKED
4432
DTT TRIP 1p. L1
DTT TRIP command - Only L1
4433
DTT TRIP 1p. L2
DTT TRIP command - Only L2
4434
DTT TRIP 1p. L3
DTT TRIP command - Only L3
4435
DTT TRIP L123
DTT TRIP command L123
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...