Functions
6-253
7SA6 Manual
C53000-G1176-C156-2
Phase Segregated
Initiation
Phase segregated initiation of the breaker failure protection is necessary if the circuit
breaker poles can be operated individually, e.g. if single-pole automatic reclosure is
used. This is possible if the device is able to trip single-pole.
If initiation of the breaker failure protection must also be possible by further external
protection devices, it is recommended, for security reasons, to connect an additional
release signal (e.g. fault detection, pickup) at the input “
>BF release
”, besides the
trip commands at the inputs “
>BF Start L1
”, “
>BF Start L2
”, and “
>BF Start
L3
”. Figure 6-126 shows the connections of this dual-channel initiation.
Nevertheless, it is possible to initiate the breaker failure protection in single-channel
mode should a separate release criterion not be available. The binary input
“>BF re-
lease
” must then not be assigned to any physical input of the device during configu-
ration.
If the external protection device does not provide a general fault detection signal, a
general trip signal can be used instead. Alternatively, the parallel connection of a sep-
arate set of trip contacts can produce such a release signal as shown in Figure
6-127.
The starting condition logic for the delay times is shown in Figure 6-128. In principle,
it is designed similar to that for the common phase initiation, but, individually for each
of the three phases. Thus, current flow and initiation conditions are processed for each
phase. In case of single-pole interruption before an automatic reclose cycle, current
disappearance is reliably monitored for the tripped breaker pole only.
Figure 6-126 Breaker failure protection with phase segregated initiation — example for initia
tion by an external protection device with release by a fault detection signal
7SA6
Trip L1
Trip L2
Trip L3
Pick-up
L+
external
prot. device
L–
>BF Start L1
>BF Start L2
>BF Start L3
>BF release
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...