Technical Data
10-46
7SA6 Manual
C53000-G1176-C156
Total storage period
max. 5 s for each fault
approx. 15 s totally
Sampling rate at f
N
= 50 Hz
1 ms
Sampling rate at f
N
= 60 Hz
0.83 ms
Statistics
Number of trip events caused by
pole segregated
7SA6
Number of automatic reclosures
initiated by the device
separate for 1-pole and 3-pole AR;
separate for 1st AR cycle
and for all further cyles
Total of interrupted currents
caused by 7SA6
pole segregated
Maximum interrupted current
pole segregated
Availability of the transmission
availability in %/min and %/h
Delay time of transmission
resolution 0.01 ms
Real Time Clock
and Buffer Battery
Resolution for operational events
1 ms
Resolution for fault events
1 ms
Buffer battery
3 V/1 Ah, type CR 1/2 AA
self-discharging time approx. 10 years