Installation and Commissioning
8-30
7SA6 Manual
C53000-G1176-C156-2
Table 8-14
Jumper setting of relay contact for BO6.
The set nominal currents of the current input transformers are checked on the input/
output board C–I/O–2. All jumpers must be set to the same nominal current, i.e. one
jumper for each input transformer (X61 to X64) and one common jumper X60.
However:
There is no jumper X64 for the version with sensitive earth current input (in-
put transformer T8).
The jumpers X71, X72 and X73 on the input/output board C–I/O–2 are for setting the
bus address and must not be changed. Table 8-15 lists the jumper presettings.
Mounting location:
for housing size
1
/
3
in Figure 8-9, slot 19,
for housing size
1
/
2
in Figure 8-10, slot 33,
for housing size
1
/
1
in Figure 8-11, slot 33 right.
Jumper
Quiescent state open
(NO contact)
Quiescent state closed
(NC contact)
Presetting
X41
1–2
2–3
1–2
Table 8-15
Jumper setting of printed circuit board addresses of binary input/output
boards C-I/O-2
Jumper
Presetting
X71
1–2 (H)
X72
1–2 (H)
X73
2–3 (L)
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...