background image

E1ZMLA10 24-240V AC/DC

www.tele-online.com

Load Alte Timer

ENYA series

5 functions

7 time ranges

Wide input voltage range

1 change over contact

Width 17.5 mm (0.69 in)

Installation design

Technical data

1. Functions

  

The funktion can be selected at anytime if connected to the supply             

      voltage.

 E 

  ON 

delay

 R 

  OFF 

delay

 L1 

  Manual 

OFF

 LA 

  Load 

Alternator 

(Pump 

Changer)

 L2 

  Manual 

ON

2. Time ranges

   Time range 

 

Adjustment range

 1 

   50 

ms 

 1 

s

 10 

s   500 

ms 

 10 

s

 1 

min 

  3 

  1 

min

 10 

min 

  30 

s  10 

min

 1 

   3 

min 

 1 

h

 10 

h   30 

min 

 10 

h

 100 

  5 

  100 

h

3. Indicators

Green LED U/t ON:   

 

indication of supply voltage

Green LED U/t flashes:   

indication of time period

Yellow LED R ON/OFF:   

indication of relay output

4. Mechanical design

Self-extinguishing plastic housing, rated IP40.
Mounted on DIN-rail TS 35 according to EN 60715
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required).  
Terminals are rated IP20
Tightening torque: max. 1 Nm (0.74 ft lbs)
Terminal capacity:
 

1 x 0.5 to 2.5 mm² (1 x 20 to 14 AWG) 

 

with/without multicore cable end 

 

1 x 4 mm² (1 x 12 AWG)

 

without multicore cable end

 

2 x 0.5 to 1.5 mm² (2 x 20 to 16 AWG) 

 

with/without multicore cable end

 

2 x 2.5 mm² (2 x 14 AWG) 

 

flexible without multicore cable end

5. Input circuit

Supply voltage:    

 

 

24 to 240V a.c./d.c.

Terminals: 

    A1(+)-A2

Tolerance:   

 

 

 

24V -15% to 240V +10%

Rated consumption:   

 

4VA (1.5W)

Rated frequency: 

 

 

a.c. 48 to 63 Hz

Duty 

cycle: 

    100 

%

Reset 

time: 

    100 

ms

Residual ripple for d.c.:   

10 %

Drop-out voltage: 

 

 

>30 % of minimum rated supply voltage

Overvoltage category: 

 

III (in accordance with IEC 60664-1)

Rated surge voltage:  

 

4kV

6. Output circuit

1 isolated change over contact (1 CO)
Contact 

material:   AgNi

Rated 

voltage: 

   250V 

a.c.

Switching capacity:   

 

2000VA (8A / 250V a.c.)

Fusing: 

     8A 

fast 

acting

Mechanical life:   

 

 

20 x 10

6

 operations

Electrical life: 

 

 

 

1 x 10

5

 operations

       at 

1000VA 

resistive 

load

Switching frequency:  

 

max. 6/min at 1000VA resistive load

       (in 

accordance 

with 

IEC 

60947-5-1)

Overvoltage category: 

 

III (in accordance with IEC 60664-1)

Rated surge voltage:  

 

4kV

7. Control input

Input not potential free:   

terminals A1-B1

Loadable: 

    yes

Max. line length:  

 

 

10 m

Trigger level (sensitivity):  

automatic adaption to supply voltage

Min. control pulse length:  

d.c. 50 ms / a.c. 100 ms

 

8. General data

Degree of protection:  

 

Basic insulation

Insulation test voltage:
 

Supply circuit - Output circuit: 1680V

Interference immunity: 

 

Class A

Prospective current value: 

1000A / 8A

8. Accuracy

Base accuracy:   

 

 

±1 % of maximum scale value

Adjustment accuracy: 

 

<5 % of maximum scale value

Repetition accuracy:   

 

<0.5 % or ±5 ms

Voltage 

influence:   -

Temperature influence:   

≤0.01 % / °C

9. Ambient conditions

Ambient temperature: 

 

-25 to +55 °C (-13 to +131 °F)

Storage temperature: 

 

-25 to +70 °C (-13 to +158 °F)

Transport temperature:   

-25 to +70 °C (-13 to +158 °F)

Relative humidity: 

 

 

15 % to 85 %

       (in 

accordance 

with 

IEC 

60721-3-3 

       class 

3K3)

Pollution degree:  

 

 

2 (in accordance with IEC 60664-1)

10. Weight

Single packing:   

 

 

80 g (2.82 oz)