2 Parameters
2.2 List of parameters
SINAMICS G130/G150
980
List Manual (LH2), 07/2016, A5E03263479A
Note:
For r9719.0 and r9719.1:
These two bits must be considered together.
- if SOS/SLS (SBH/SG) is de-selected using bit 0, then assignment of bit 1 is irrelevant.
- if SOS/SLS (SBH/SG) is selected using bit 0, then a changeover is made between SOS (SBH) and SLS (SG) using
bit 1.
SLP: Safely Limited Position / SE: Safe software limit switches
SLS: Safely Limited Speed / SG: Safely reduced speed
SOS: Safe Operating Stop / SBH: Safe operating stop
SDI: Safe Direction (safe motion direction)
Description:
Control signals for safety-relevant motion monitoring functions integrated in the drive.
Note:
This parameter is only supplied with actual values in the case of Safety Integrated Extended Functions. For Safety
Integrated Basic Functions (SBC, SS1, STO), the value is equal to zero.
08
Gearbox selection bit 0
Set
Not set
-
09
Gearbox selection bit 1
Set
Not set
-
10
Gearbox selection bit 2
Set
Not set
-
11
Gearbox switchover
Set
Not set
-
12
Select SLP (SE) position range
SLP2 (SE2)
SLP1 (SE1)
-
13
Close brake from control
Yes
No
-
15
Select test stop
Yes
No
-
16
SGE valid
Yes
No
-
18
De-select external STOP A
Yes
No
-
19
De-select external STOP C
Yes
No
-
20
De-select external STOP D
Yes
No
-
21
De-select external STOP E
Yes
No
-
28
SLS (SG) override bit 0
Set
Not set
-
29
SLS (SG) override bit 1
Set
Not set
-
30
SLS (SG) override bit 2
Set
Not set
-
31
SLS (SG) override bit 3
Set
Not set
-
r9720.0...28
CO/BO: SI Motion control signals integrated in the drive / SI Mtn integ STW
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
2840, 2905
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
De-select STO
Yes
No
-
01
De-select SS1
Yes
No
-
02
De-select SS2
Yes
No
-
03
De-select SOS
Yes
No
-
04
De-select SLS
Yes
No
-
06
Deselect SLP
Yes
No
2822
07
Acknowledgment
Signal edge active
No
-
09
Select SLS bit 0
Set
Not set
-
10
Select SLS bit 1
Set
Not set
-
12
Deselect SDI positive
Yes
No
2824
13
Deselect SDI negative
Yes
No
2824
19
Select SLP position range
SLP2
SLP1
2822
24
Select gearbox bit 0
Set
Not set
-
25
Select gearbox bit 1
Set
Not set
-
26
Select gearbox bit 2
Set
Not set
-
27
Gearbox switchover
Set
Not set
-
28
Deselect SS2E
Yes
No
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......