SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
69
2 Parameters
2.2 List of parameters
Description:
Displays the torque utilization as a percentage.
The torque utilization is obtained from the required smoothed torque referred to the torque limit.
Dependency:
Refer to: r0033
Note:
The torque utilization is available smoothed (r0033) and unsmoothed (r0081).
The torque utilization is obtained from the required torque referred to the torque limit as follows:
- Positive torque: r0081 = (r0079 / r1538) * 100 %
- Negative torque: r0081 = (-r0079 / -r1539) * 100 %
Description:
Displays the instantaneous active power.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Electric power
Dependency:
Refer to: r0032
Note:
The mechanical active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed
(r0082[0]).
Description:
Displays the instantaneous active power.
Dependency:
Refer to: r0032
Notice:
For Basic Line Modules of chassis format, the displayed value is invalid as these units do not have any current
sensing.
Note:
The active power is available smoothed (r0032) and unsmoothed (r0082).
Description:
Displays the flux setpoint.
r0081
CO: Torque utilization / M_Utilization
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
8012
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- [%]
- [%]
- [%]
r0082[0...2]
CO: Active power actual value / P_act
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6714, 6799
P-Group:
Displays, signals
Unit group:
14_5
Unit selection:
p0505
Not for motor type:
-
Scaling:
r2004
Expert list:
1
Min Max
Factory
setting
- [kW]
- [kW]
- [kW]
r0082
CO: Active power actual value / P_act
B_INF
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
8750, 8850,
8950
P-Group:
Displays, signals
Unit group:
14_7
Unit selection:
p0505
Not for motor type:
-
Scaling:
r2004
Expert list:
1
Min Max
Factory
setting
- [kW]
- [kW]
- [kW]
r0083
CO: Flux setpoint / Flex setp
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- [%]
- [%]
- [%]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......