SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
941
2 Parameters
2.2 List of parameters
Description:
Sets the lower limit for the function "Safely Limited Position" (SLP).
Index:
[0] = Limit value SLP1 (SE1)
[1] = Limit value SLP2 (SE2)
Dependency:
Refer to: p9501, p9534, p9562
Refer to: C01715
Note:
The following applies to the setting of these limits:
- p9534[x] > p9535[x]
- p9535[x] must lie in the valid traversing range (-737280 ... 737280).
SLP: Safely Limited Position / SE: Safe software limit switches
Description:
Sets the lower limit for the function "Safely Limited Position" (SLP).
Index:
[0] = Limit value SLP1 (SE1)
[1] = Limit value SLP2 (SE2)
Dependency:
Refer to: p9501, p9534, p9562
Refer to: C01715
Note:
The following applies to the setting of these limits:
- p9534[x] > p9535[x]
- p9535[x] must lie in the valid traversing range (-737280 ... 737280).
SLP: Safely Limited Position / SE: Safe software limit switches
Description:
Sets the plus cam position for the function "Safe Cam" (SCA).
Index:
[0] = Cam position SCA1 (SN1)
[1] = Cam position SCA2 (SN2)
[2] = Cam position SCA3 (SN3)
[3] = Cam position SCA4 (SN4)
[4] = Cam position SCA5 (SN5)
[5] = Cam position SCA6 (SN6)
[6] = Cam position SCA7 (SN7)
[7] = Cam position SCA8 (SN8)
[8] = Cam position SCA9 (SN9)
[9] = Cam position SCA10 (SN10)
[10] = Cam position SCA11 (SN11)
[11] = Cam position SCA12 (SN12)
[12] = Cam position SCA13 (SN13)
p9535[0...1]
SI Motion SLP (SE) lower limit values (Control Unit) / SI Mtn SLP low lim
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2822
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-2147000.000 [mm]
2147000.000 [mm]
-100000.000 [mm]
p9535[0...1]
SI Motion SLP (SE) lower limit values (Control Unit) / SI Mtn SLP low lim
VECTOR_G (Safety
rot)
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2822
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-2147000.000 [°]
2147000.000 [°]
-100000.000 [°]
p9536[0...29]
SI Motion SCA (SN) plus cam position (Control Unit) / SI Mtn SCA+
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-2147000.000 [mm]
2147000.000 [mm]
10.000 [mm]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......