2 Parameters
2.2 List of parameters
SINAMICS G130/G150
50
List Manual (LH2), 07/2016, A5E03263479A
Description:
Displays the smoothed absolute actual current value.
Dependency:
Refer to: r0068
Notice:
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
For Basic Line Modules of chassis format, the displayed value is invalid as these units do not have any current
sensing.
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The absolute current actual value is available smoothed (r0027) and unsmoothed (r0068).
Description:
Displays the smoothed actual value of the modulation depth.
Dependency:
Refer to: r0074
Note:
A_INF: Smoothing time constant = 300 ms
SERVO, VECTOR: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
Description:
Displays the smoothed field-generating actual current.
Dependency:
Refer to: r0076
Note:
SERVO: Smoothing time constant = 100 ms
VECTOR: Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
r0027
CO: Absolute actual current smoothed / I_act abs val smth
B_INF
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
8750
P-Group:
Displays, signals
Unit group:
6_4
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2002
Expert list:
1
Min Max
Factory
setting
- [A]
- [A]
- [A]
r0028
Modulation depth smoothed / Mod_depth smth
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
5730, 6799,
8950
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2002
Expert list:
1
Min Max
Factory
setting
- [%]
- [%]
- [%]
r0029
Current actual value field-generating smoothed / Id_act smooth
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
5730, 6799
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2002
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......