2 Parameters
2.2 List of parameters
Description:
Sets the alarm threshold for monitoring the motor temperature for motor temperature models 1 and 3.
The stator winding temperature (r0632) is used to initiate the signal.
The following applies for temperature model 1 (I2t):
- only effective from firmware version 4.7 SP6 and p0612.8 = 1.
- Alarm A07012 is output after the alarm threshold is exceeded.
- when commissioning a catalog motor for the first time, the threshold value is copied from p0605 to p5390.
The following applies for temperature model 3:
- after the alarm threshold is exceeded, alarm A07012 is output and a calculated delay time (t = p5371/p5381) is
started.
- if the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011
is output.
Dependency:
Refer to: r0034, p0605, p0612, r0632, p5391
Refer to: F07011, A07012, A07014
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis is 2 K.
Description:
Sets the fault threshold for monitoring the motor temperature for motor temperature models 1 and 3.
Fault F07011 is output after the fault threshold is exceeded.
The stator winding temperature (r0632) is used to initiate the signal.
The following applies for temperature model 1 (I2t):
- only effective from firmware version 4.7 SP6 and p0612.8 = 1.
- when commissioning a catalog motor for the first time, the threshold value is copied from p0615 to p5391.
Dependency:
Refer to: r0034, p0612, p0615, r0632, p5390
Refer to: F07011, A07014
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis is 2 K.
Description:
Displays the ambient temperature for motor temperature model 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p0613.
p5390[0...n]
Mot_temp_mod 1/3 alarm threshold / A thresh
VECTOR_G
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
8017
P-Group:
Motor
Unit group:
21_1
Unit selection:
p0505
Not for motor type:
ASM, SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [°C]
200.0 [°C]
110.0 [°C]
p5391[0...n]
Mot_temp_mod 1/3 fault threshold / F thresh
VECTOR_G
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
8017
P-Group:
Motor
Unit group:
21_1
Unit selection:
p0505
Not for motor type:
ASM, SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [°C]
200.0 [°C]
120.0 [°C]
r5397
Mot_temp_mod 3 ambient temperature image p0613 / AmbTmp image p0613
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
8019
P-Group:
Displays, signals
Unit group:
21_1
Unit selection:
p0505
Not for motor type:
ASM, SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......