2 Parameters
2.2 List of parameters
SINAMICS G130/G150
442
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the proportional gain of the current controller for the lower adaptation current range.
This value is automatically pre-set using p3900 or p0340 when commissioning has been completed.
Dependency:
Refer to: p0391, p0392, p0393
Note:
For p0393 = 100 %, the current controller adaptation is disabled and p1715 is effective over the entire range.
Description:
Sets the integral-action time of the current controller.
Dependency:
Refer to: p1715
Description:
Displays the actual output of the Isq current controller (torque/force generating current, PI controller).
The value contains the proportional and integral components of the PI controller.
Description:
Displays the integral component of the Isq current controller (torque/force-generating current, PI controller).
p1715[0...n]
Current controller P gain / I_ctrl Kp
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6700, 6714,
7017
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 100000.000
0.000
p1717[0...n]
Current controller integral-action time / I_ctrl Tn
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
5714, 6700,
6714, 7017
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
1000.00 [ms]
2.00 [ms]
r1718
CO: Isq controller output / Isq_ctrl outp
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6714
P-Group:
Closed-loop control
Unit group:
5_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
r1719
Isq controller integral component / Isq_ctrl I_comp
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6714
P-Group:
Closed-loop control
Unit group:
5_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......