SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1675
4 Faults and alarms
4.2 List of faults and alarms
F30600
SI P2: STOP A initiated
Message value:
%1
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
VECTOR_G
Component:
None
Propagation:
LOCAL
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function in monitoring channel 2 has detected a fault and initiated a STOP A
(STO via the safety switch-off signal path of monitoring channel 2).
- forced checking procedure (test stop) of the safety switch-off signal path of monitoring channel 2 unsuccessful.
- subsequent response to fault F30611 (defect in a monitoring channel).
Fault value (r0949, interpret decimal):
0: Stop request from the Control Unit.
1005: STO active although STO not selected and there is no internal STOP A present.
1010: STO inactive although STO is selected or an internal STOP A is present.
1011: internal error for STO deselected in monitoring channel 2.
1020: Internal software error in the "Internal voltage protection" function. The "internal voltage protection" function is
withdrawn. A STOP A that cannot be acknowledged is initiated.
9999: Subsequent response to fault F30611.
Remedy:
- select Safe Torque Off and de-select again.
- carry out a POWER ON (switch-off/switch-on) for all components.
- replace the Motor Module/Hydraulic Module involved.
For fault value = 1020:
- upgrade the Motor Module/Hydraulic Module software.
- replace the Motor Module/Hydraulic Module.
For fault value = 9999:
- carry out diagnostics for fault F30611.
Note:
CU: Control Unit
MM: Motor Module
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
F30611 (A)
SI P2: Defect in a monitoring channel
Message value:
%1
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
VECTOR_G
Component:
None
Propagation:
LOCAL
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on processor 2 has detected a fault in the crosswise data
comparison between the two monitoring channels and has initiated a STOP F.
As a result of this fault, after the parameterized transition has expired (p9858), fault F30600 is output (SI MM: STOP
A initiated).
Fault value (r0949, interpret decimal):
0: Stop request from the other monitoring channel.
1 ... 999:
Number of the cross-compared data that resulted in this fault. This number is also displayed in r9895.
1: SI monitoring clock cycle (r9780, r9880).
2: SI enable safety functions (p9601, p9801). Crosswise data comparison is only carried out for the supported bits.
3: SI SGE changeover discrepancy time (p9650, p9850).
4: SI transition period STOP F to STOP A (p9658, p9858).
5: SI enable Safe Brake Control (p9602, p9802).
6: SI Motion enable, safety-relevant functions (p9501, internal value).
7: SI delay time of STO for Safe Stop 1 (p9652, p9852).
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......