SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
261
2 Parameters
2.2 List of parameters
Description:
Sets the mode for the test sockets.
Value:
96:
Physical address (32-bit integer signal unsigned)
97:
Physical address (32-bit integer signal)
98:
Physical address (32-bit floating-point signal)
99:
BICO signal
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Refer to: p0771, r0772, r0774, p0777, p0778, p0779, p0780, p0783, p0784, r0786, p0788, p0789, r0790
Description:
The scaling characteristic for the test sockets is defined using two points.
This parameter specifies the x coordinate (percentage) of the first point on the characteristic.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Can only be set when p0776 = 99.
Refer to: p0778, p0779, p0780, r0786
Note:
The value 0.00 % corresponds to 2.49 V.
Description:
The scaling characteristic for the test sockets is defined using two points.
This parameter specifies the y coordinate (output voltage) of the first point on the characteristic.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Can only be set when p0776 = 99.
Refer to: p0777, p0779, p0780, r0786
p0776[0...2]
Test socket mode / Test skt mode
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Integer16
Dyn. index:
-
Func. diagram:
8134
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
96 99
99
p0777[0...2]
Test socket characteristic value x1 / Test skt char x1
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
8134
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-100000.00 [%]
100000.00 [%]
0.00 [%]
p0778[0...2]
Test socket characteristic value y1 / Test skt char y1
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
8134
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [V]
4.98 [V]
2.49 [V]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......