SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1893
4 Faults and alarms
4.2 List of faults and alarms
A35413 (F, N)
TM: Temperature alarm threshold channel 7 exceeded
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
B_INF, TM150, VECTOR_G
Component:
Terminal Module (TM)
Propagation:
BICO
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[7]) measured using the temperature sensing of the Terminal Module 150 (TM150) has
exceeded the threshold value to initiate this alarm (p4102[14]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[7] = 1, 4), the following applies:
- if r4101[7] > 1650 ohms, the temperature r4105[7] = 250 °C
- if r4101[7] <= 1650 ohms, the temperature r4105[7] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[14] - hysteresis (p4118[7]).
See also: p4102
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35414 (F, N)
TM: Temperature alarm threshold channel 8 exceeded
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
B_INF, TM150, VECTOR_G
Component:
Terminal Module (TM)
Propagation:
BICO
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[8]) measured using the temperature sensing of the Terminal Module 150 (TM150) has
exceeded the threshold value to initiate this alarm (p4102[16]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[8] = 1, 4), the following applies:
- if r4101[8] > 1650 ohms, the temperature r4105[8] = 250 °C
- if r4101[8] <= 1650 ohms, the temperature r4105[8] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[16] - hysteresis (p4118[8]).
See also: p4102
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35415 (F, N)
TM: Temperature alarm threshold channel 9 exceeded
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
B_INF, TM150, VECTOR_G
Component:
Terminal Module (TM)
Propagation:
BICO
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[9]) measured using the temperature sensing of the Terminal Module 150 (TM150) has
exceeded the threshold value to initiate this alarm (p4102[18]).
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......