2 Parameters
2.2 List of parameters
SINAMICS G130/G150
1064
List Manual (LH2), 07/2016, A5E03263479A
Dependency:
Refer to: p10230, p10235
Note:
The test sequence is selected using p10230[4] or p10235.4.
Description:
Sets the tolerated position deviation for sequence 2 for the safe brake test.
Index:
[0] = Brake 1
[1] = Brake 2
Dependency:
Refer to: p10230, p10235
Note:
The test sequence is selected using p10230[4] or p10235.4.
Description:
Sets the signal sources for the control word of the safe brake test
This parameter is only valid for "SBT via BICO" (p10203 = 1).
Index:
[0] = Select brake test
[1] = Start brake test
[2] = Select brake
[3] = Select test torque sign
[4] = Select test sequence
[5] = External brake status
Note:
For BI: p10230[0]:
0/1 signal: select brake test.
0 signal: inactive.
For BI: p10230[1]:
0/1 signal: start brake test.
For BI: p10230[2]:
1 signal: select brake 2.
0 signal: select brake 1.
For BI: p10230[3]:
1 signal: select negative test torque.
0 signal: select positive test torque.
For BI: p10230[4]:
1 signal: select test sequence 2.
0 signal: select test sequence 1.
For BI: p10230[5]:
1 signal: external brake closed.
0 signal: external brake open.
p10222[0...1]
SI Motion SBT position tolerance sequence 2 / SBT pos_tol seq 2
VECTOR_G (Safety
rot)
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2836
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.001 [°]
360.000 [°]
1.000 [°]
p10230[0...5]
BI: SI Motion SBT control word / SBT STW
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
2837
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......