2 Parameters
2.2 List of parameters
SINAMICS G130/G150
472
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the motor data identification and speed controller optimization.
p1900 = 0:
Function inhibited.
p1900 = 2:
Induction motors --> set p1910 = 1 and p1960 = 0
Permanent-magnet or separately excited synchronous motors --> set p1910 = 1, p1990 = 1 and p1960 = 0
When the drive enable signals are present, a motor data identification routine is carried out at standstill with the next
switch-on command. Current flows through the motor which means that it can align itself by up to a quarter of a
revolution.
For permanent-magnet or separately excited synchronous motors, the encoder is adjusted with the next switch-on
command. The motor must be free to rotate and rotates through 1.5 revolutions of the motor encoder.
Value:
0:
Inhibited
2:
Identifying motor data (at standstill)
Dependency:
In the simulation mode, the parameter cannot be written into.
When selecting the motor data identification routine, the drive data set changeover is suppressed.
Refer to: p1272, p1300, p1910
Refer to: F07990, A07991
Notice:
If there is a motor holding brake, it must be open (p1215 = 2).
To permanently accept the determined settings they must be saved in a non-volatile fashion (p0971, p0977).
It is not permissible to activate write protection during the motor identification (p7761).
During the rotating measurement it is not possible to save the parameters (p0971, p0977).
Note:
The motor and control parameters of the vector control are only optimally set when both measurements are carried
out (initially at standstill, and then with the motor rotating). The measurement with rotating motor is not performed for
p1300 < 20 (U/f controls).
An appropriate alarm is output when the parameter is set.
The switch-on command must remain set during a measurement and after the measurement has been completed,
the drive automatically resets it.
The duration of the measurements can lie between 0.3 s and several minutes. This time is, for example, influenced
by the motor size and the mechanical conditions.
p1900 is automatically set to 0 after the motor data identification routine has been completed.
If a reluctance motor has been parameterized, a pole position identification is carried out during the stationary
measurement. As a consequence, faults that occur can also be assigned to the pole position identification.
Description:
Sets the motor data identification and speed controller optimization.
The motor identification should first be performed with the motor stationary (p1900 = 1, 2; also refer to p1910). Based
on this, additional motor and control parameters can be determined using the motor data identification with the motor
rotating (p1900 = 1, 3; also refer to p1960); not for p1300 < 20.
p1900 = 0:
Function inhibited.
p1900
Motor data identification and rotating measurement / MotID and rot meas
VECTOR_G
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Motor identification
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 2
2
p1900
Motor data identification and rotating measurement / MotID and rot meas
VECTOR_G (n/M)
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Motor identification
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
2
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......