SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1041
2 Parameters
2.2 List of parameters
Description:
Sets the fail-safe digital input (F-DI) for the "STO" function (operating mode "control interface").
Value:
0:
Static selected
1:
F-DI 0 (X521.2/3/6)
2:
F-DI 1 (X521.4/5/7)
3:
F-DI 2 (X522.1/2/7)
4:
F-DI 3 (X522.3/4/8)
5:
F-DI 4 (X522.5/6/9)
6:
F-DI 5 (X531.2/3/6)
7:
F-DI 6 (X531.4/5/7)
8:
F-DI 7 (X532.1/2/7)
9:
F-DI 8 (X532.3/4/8)
10:
F-DI 9 (X532.5/6/9)
255:
Static deselected
Index:
[0] = Drive group 1
[1] = Drive group 2
[2] = Drive group 3
[3] = Drive group 4
Note:
If value = 0:
No terminal assigned, safety function always selected.
If value = 255:
No terminal assigned, safety function always deselected.
F-DI: Failsafe Digital Input
STO: Safe Torque Off
Description:
Sets the fail-safe digital input (F-DI) for the "SS1" function (operating mode "control interface").
Value:
0:
Static selected
1:
F-DI 0 (X521.2/3/6)
2:
F-DI 1 (X521.4/5/7)
3:
F-DI 2 (X522.1/2/7)
4:
F-DI 3 (X522.3/4/8)
5:
F-DI 4 (X522.5/6/9)
6:
F-DI 5 (X531.2/3/6)
7:
F-DI 6 (X531.4/5/7)
8:
F-DI 7 (X532.1/2/7)
9:
F-DI 8 (X532.3/4/8)
10:
F-DI 9 (X532.5/6/9)
255:
Static deselected
Index:
[0] = Drive group 1
[1] = Drive group 2
[2] = Drive group 3
[3] = Drive group 4
Note:
If value = 0:
No terminal assigned, safety function always selected.
p10022[0...3]
SI TM54F STO input terminal / SI STO F-DI
TM54F_MA,
TM54F_SL
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2900, 2905
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 255
0
p10023[0...3]
SI TM54F SS1 input terminal / SI SS1 F-DI
TM54F_MA,
TM54F_SL
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2900, 2905
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 255
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......