957
2 Parameters
2.2 List of parameters
Description:
Sets the delay time for the function "Safe motion direction" (SDI).
After selecting the SDI function, then for a maximum of this time, motion in the monitored direction is permissible.
This time can therefore be used for braking any motion.
Dependency:
Refer to: p9564, p9566
Refer to: C01716
Note:
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
SDI: Safe Direction (safe motion direction)
Description:
Sets the stop response for the function "Safe motion direction" (SDI).
This setting applies to both directions of motion.
Value:
0:
STOP A
1:
STOP B
2:
STOP C
3:
STOP D
4:
STOP E
10:
STOP A with delayed stop response when the bus fails
11:
STOP B with delayed stop response when the bus fails
12:
STOP C with delayed stop response when the bus fails
13:
STOP D with delayed stop response when the bus fails
14:
STOP E with delayed stop response when the bus fails
Dependency:
Refer to: p9564, p9565
Refer to: C01716
Notice:
In the case of encoderless motion monitoring (p9506 = 1), only a value of 0 or 1 is permitted.
Note:
In the extended sense, a bus failure should be seen here as a communication error in the control signals of the safety
functions (e.g. via PROFIsafe or TM54F).
SDI: Safe Direction (safe motion direction)
Description:
Sets the velocity limit for the "SAM" and "SBR" functions.
SAM is deactivated once the set velocity limit has been undershot.
SBR is deactivated if the safe brake ramp falls below the set velocity limit.
Note:
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SBR: Safe Brake Ramp (safe brake ramp monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
p9565
SI Motion SDI delay time (Control Unit) / SI Mtn SDI t CU
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2824
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
600000.00 [ms]
100.00 [ms]
p9566
SI Motion SDI stop response (Control Unit) / SI Mtn SDI Stop CU
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2824
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 14
1
p9568
SI Motion SAM/SBR velocity limit (Control Unit) / SI Mtn SAM v_limCU
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [mm/min]
1000.00 [mm/min]
0.00 [mm/min]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......