2 Parameters
2.2 List of parameters
SINAMICS G130/G150
768
List Manual (LH2), 07/2016, A5E03263479A
Note:
The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 2:
1. Switch off the system and replace valve 2.
2. Switch on the system and acknowledge that valve 2 has been replaced (p7786.2 = 1).
--> the power cycling counter of valve 2 is reset (r7741 = 0).
3. Carry out a POWER ON (switch-off/switch-on).
--> as a consequence p7786.2 is automatically set to 0.
Description:
Displays the status of power cycling counter for valve 3.
For repairs, this parameter serves as internal documentation for service personnel.
The counter state corresponds to the valve wear. A maximum of 650% of the specified service life is displayed.
Dependency:
Refer to: p7786
Notice:
After a valve has been replaced, the corresponding power cycling counter must be reset.
Note:
The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 3:
1. Switch off the system and replace valve 3.
2. Switch on the system and acknowledge that valve 3 has been replaced (p7786.3 = 1).
--> the power cycling counter of valve 3 is reset (r7742 = 0).
3. Carry out a POWER ON (switch-off/switch-on).
--> as a consequence p7786.3 is automatically set to 0.
Description:
Displays the status of power cycling counter for valve 4.
For repairs, this parameter serves as internal documentation for service personnel.
The counter state corresponds to the valve wear. A maximum of 650% of the specified service life is displayed.
Dependency:
Refer to: p7786
Notice:
After a valve has been replaced, the corresponding power cycling counter must be reset.
Note:
The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 4:
1. Switch off the system and replace valve 4.
2. Switch on the system and acknowledge that valve 4 has been replaced (p7786.4 = 1).
--> the power cycling counter of valve 4 is reset (r7743 = 0).
3. Carry out a POWER ON (switch-off/switch-on).
--> as a consequence p7786.4 is automatically set to 0.
r7742[0...n]
IGBT power cycling counter valve 3 / IGBT load count 3
VECTOR_G, B_INF
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Unsigned16
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r7743[0...n]
IGBT power cycling counter valve 4 / IGBT load count 4
VECTOR_G, B_INF
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Unsigned16
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......