2 Parameters
2.2 List of parameters
SINAMICS G130/G150
314
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the signal source to change over from manual to automatic when using a motorized potentiometer.
In the manual mode, the setpoint is changed using two signals - raise and lower. In the automatic mode, the setpoint
must be interconnected via a connector input.
Dependency:
Refer to: p1030, p1035, p1036, p1042
Note:
The effectiveness of the internal ramp-function generator can be set in automatic mode.
Description:
Sets the signal source for the setpoint of the motorized potentiometer in the automatic mode.
Dependency:
Refer to: p1041
Description:
Sets the signal source to accept the setting value for the motorized potentiometer.
Dependency:
Refer to: p1044
Note:
The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
Description:
Sets the signal source for the setting value for the motorized potentiometer.
Dependency:
Refer to: p1043
Note:
The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
p1041[0...n]
BI: Motorized potentiometer manual/automatic / Mop manual/auto
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
3020
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p1042[0...n]
CI: Motorized potentiometer automatic setpoint / Mop auto setpoint
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
3020
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- -
0
p1043[0...n]
BI: Motorized potentiometer accept setting value / MotP acc set val
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
3020
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p1044[0...n]
CI: Motorized potentiometer setting value / Mop set val
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
3020
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......