2 Parameters
2.2 List of parameters
SINAMICS G130/G150
618
List Manual (LH2), 07/2016, A5E03263479A
Description:
Displays the target frequency for the line-drive synchronization.
Dependency:
Refer to: A07941
Description:
Displays the frequency difference between the measured target frequency and output frequency of the gating unit of
the closed-loop control for line-drive synchronization.
Description:
Sets the threshold value of the frequency difference to activate the closed-loop phase control for line-drive
synchronization.
The closed-loop phase control is activated (r3819.6 = 1), if the frequency difference is less that the threshold value.
Description:
Displays the phase difference between the measured target phase and phase of the gating unit of the closed-loop
control for line-drive synchronization.
Description:
Sets the phase setpoint for the line-drive synchronization.
r3804
CO: Sync-line-drive target frequency / Sync f_target
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
3030, 7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
r3805
CO: Sync-line-drive frequency difference / Sync f_diff
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
p3806[0...n]
Sync-line-drive frequency difference threshold value / Sync f_diff thresh
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Hz]
1.00 [Hz]
0.10 [Hz]
r3808
CO: Sync-line-drive phase difference / Sync phase diff
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2005
Expert list:
1
Min Max
Factory
setting
- [°]
- [°]
- [°]
p3809[0...n]
Sync-line-drive phase setpoint / Sync phase setp
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-180.00 [°]
179.90 [°]
0.00 [°]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......