2 Parameters
2.2 List of parameters
SINAMICS G130/G150
914
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the tolerance for the function "Safe motion direction" (SDI).
This motion in the monitored direction is still permissible before safety message C30716 is initiated.
Dependency:
Refer to: p9365, p9366
Refer to: C30716
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SDI: Safe Direction (safe motion direction)
Description:
Sets the tolerance for the function "Safe motion direction" (SDI).
This motion in the monitored direction is still permissible before safety message C30716 is initiated.
Dependency:
Refer to: p9365, p9366
Refer to: C30716
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SDI: Safe Direction (safe motion direction)
Description:
Sets the delay time for the function "Safe motion direction" (SDI).
After selecting the SDI function, then for a maximum of this time, motion in the monitored direction is permissible.
This time can therefore be used for braking any motion.
Dependency:
Refer to: p9364, p9366
Refer to: C30716
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
SDI: Safe Direction (safe motion direction)
p9364
SI Motion SDI tolerance (Motor Module) / SI Mtn SDI tol MM
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2824
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.001 [mm]
360.000 [mm]
12.000 [mm]
p9364
SI Motion SDI tolerance (Motor Module) / SI Mtn SDI tol MM
VECTOR_G (Safety
rot)
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2824
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.001 [°]
360.000 [°]
12.000 [°]
p9365
SI Motion SDI delay time (Motor Module) / SI Mtn SDI t MM
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2824
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [µs]
600000000.00 [µs]
100000.00 [µs]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......