2 Parameters
2.2 List of parameters
p1134 = 1 (discontinuous smoothing)
If the setpoint is reduced while ramping-up, then the output goes immediately in the direction of the new setpoint. For
the setpoint change there is no rounding-off.
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note:
This time can be exceeded if the DC link voltage reaches its maximum value.
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
Description:
Sets the final rounding-off time for OFF3 for the extended ramp generator.
Description:
Sets the signal source for scaling the ramp-up time of the ramp-function generator.
Dependency:
Refer to: p1120
Note:
The ramp-up time is set in p1120.
Description:
Sets the signal source for scaling the ramp-down time of the ramp-function generator.
Dependency:
Refer to: p1121
Note:
The ramp-down time is set in p1121.
p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
VECTOR_G
Can be changed:
C2(1), U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3060, 3070
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
600.000 [s]
3.000 [s]
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3070
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
30.000 [s]
0.000 [s]
p1137[0...n]
OFF3 final rounding-off time / RFG OFF3 t_end_del
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3070
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
30.000 [s]
0.000 [s]
p1138[0...n]
CI: Ramp-function generator ramp-up time scaling / RFG t_RU scal
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
3060, 3070
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
1
p1139[0...n]
CI: Ramp-function generator ramp-down time scaling / RFG t_RD scal
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
3060, 3070
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
1
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......