2 Parameters
2.2 List of parameters
SINAMICS G130/G150
422
List Manual (LH2), 07/2016, A5E03263479A
Description:
Display and connector output for the output of the field weakening controller (synchronous motor) or the output of the
flux controller (separately excited synchronous motor, induction motor).
Index:
[0] = PI output
[1] = I output
Description:
Sets the P gain of the field-weakening controller.
Description:
Sets an additional setpoint for the field weakening controller.
The value refers to the dynamic voltage reserve (p1574).
Note:
For a value equal to zero, the field weakening controller is activated when the maximum voltage, calculated with the
average value of the DC link voltage - and limited using p1575 - is reached.
Positive values mean that the field weakening controller intervenes later.
Negative values cause the field weakening controller to intervene earlier, so that the voltage can move away from the
modulation depth limit.
Description:
Sets the integral-action time of the field-weakening controller.
r1593[0...1]
CO: Field weakening controller / flux controller output / Field/Fl_ctrl outp
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6723, 6724,
6726
P-Group:
Closed-loop control
Unit group:
6_2
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2002
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
p1594[0...n]
Field-weakening controller P gain / Field_ctrl Kp
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6724
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
ASM, SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 1000.00
0.00
p1595[0...n]
Field weakening controller additional setpoint / Field_ctr add_setp
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6726
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-80.00 [%]
50.00 [%]
0.00 [%]
p1596[0...n]
Field weakening controller integral-action time / Field_ctrl Tn
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6723, 6724
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
10 [ms]
10000 [ms]
50 [ms]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......