SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
289
2 Parameters
2.2 List of parameters
Description:
Display and BICO output for the status word of the sequence control of the infeed unit.
Note:
For bits 00, 01, 02, 04, 06, 09:
For PROFIdrive, these signals are used for status word 1.
Description:
Displays the status word for sequence control on the encoder drive object.
Note:
For PROFIdrive, this signal is used for status word ZSW2_ENC.
Description:
Displays or sets the PROFIBUS address for PROFIBUS interface on the Control Unit.
The address can be set as follows:
1) Using the address switch on the Control Unit.
--> p0918 can then only be read and displays the selected address.
--> A change only becomes effective after a POWER ON.
2) Using p0918
--> Only if the address 00 hex, 7F hex, 80 hex, or FF hex has been set using the address switch.
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note:
Permissible PROFIBUS addresses: 1 ... 126 (01 hex ... 7E hex)
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
r0899.0...12
CO/BO: Status word sequence control infeed / ZSW seq_ctrl INF
B_INF
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
8726
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Ready for switching on
Yes
No
-
01
Ready
Yes
No
-
02
Operation enabled
Yes
No
-
04
No OFF2 active
OFF2 inactive
OFF2 active
-
06
Switching-on inhibited
Yes
No
-
08
Switching-on operation active
Yes
No
-
09
Control request
Yes
No
-
11
Precharging complete
Yes
No
-
12
Line contactor closed
Yes
No
-
r0899.7...9
CO/BO: Status word sequence control encoder DO / ZSW seq_ctrl encDO
ENC
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
07
Drive ready
Yes
No
-
09
Control request
Yes
No
-
p0918
PROFIBUS address / PB address
CU_G130_DP,
CU_G150_DP
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
2401, 2410
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 126
126
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......