SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1061
2 Parameters
2.2 List of parameters
Description:
Selects the motor type for the safe brake test.
Value:
0:
Rotating
1:
Linear
Dependency:
Refer to: F01787
Note:
For safe functions that are not enabled (p9501 = 0), the following applies:
- p10204 is automatically set the same as r0108.12 when the system boots.
When the safe brake test is enabled (10201.0 = 1), the following applies:
- p10204 is checked when the system boots to see that it matches r0108.12.
Description:
Sets the time, during which the test torque is ramped up against the closed brake.
The test torque is then ramped down after the safe brake test.
Index:
[0] = Brake 1
[1] = Brake 2
Note:
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
Description:
Sets the effective holding torque on the motor side of the brake to be tested.
Index:
[0] = Brake 1
[1] = Brake 2
Dependency:
The holding torque of an external brake should be converted to the motor side.
Conversion factor:
- motor type = rotary and axis type = linear: p9522 / (p9521 x p9520)
- otherwise: p9522 / p9521
Further, the efficiency of the mechanical system should be taken into account.
Refer to: p10210, p10220
Note:
The test torque effective for the brake test can be set for each sequence using a factor (p10210, p10220).
p10204
SI Motion SBT motor type / SBT motor type
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p10208[0...1]
SI Motion SBT test torque ramp time / SBT M_test t_ramp
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2836
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
20 [ms]
10000 [ms]
1000 [ms]
p10209[0...1]
SI Motion SBT brake holding torque / SBT brake M_stop
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2836
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1.00 [Nm]
60000.00 [Nm]
10.00 [Nm]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......