2 Parameters
2.2 List of parameters
SINAMICS G130/G150
444
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the scaling of the quadrature arm decoupling
Note:
This parameter is ineffective for sensorless vector control. In this case, p1727 is always used. If p1726 is set to 0,
then the quadrature de-coupling is deactivated. The integral component of the Isd current controller remains effective
in the complete speed control range.
For the closed-loop control of synchronous motors, this parameter is used to scale the current controller de-coupling.
Description:
Sets the scaling of quadrature arm decoupling when the voltage limit is reached.
Description:
Displays the actual output of the quadrature channel de-coupling for the d axis.
Description:
Displays the actual output of the quadrature channel de-coupling for the q axis.
Description:
Sets the speed threshold for deactivating the integral component of the Isd controller.
The d current controller is only effective as P controller for speeds greater than the threshold value. Instead of the
integral component, the quadrature arm decoupling is effective.
p1726[0...n]
Quadrature arm decoupling scaling / Transv_decpl scal
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6714
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
200.0 [%]
75.0 [%]
p1727[0...n]
Quadrature arm decoupling at voltage limit scaling / TrnsvDecplVmaxScal
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6714
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
200.0 [%]
50.0 [%]
r1728
De-coupling voltage in-line axis / U_dir-axis_decoupl
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6714
P-Group:
Closed-loop control
Unit group:
5_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
r1729
De-coupling voltage quadrature axis / U_quad_decoupl
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6714
P-Group:
Closed-loop control
Unit group:
5_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
p1730[0...n]
Isd controller integral component shutdown threshold / Isd ctrl Tn shutd
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
PMSM, SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
30 [%]
150 [%]
30 [%]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......