SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
999
2 Parameters
2.2 List of parameters
Description:
Sets the additional field-generating current for synchronous motors with sensorless actual value sensing.
The set value is referred to p0305.
This parameter ensures a "base load" for the motor.
The value must fulfill the following condition:
|p0305 x p9783| >= p9588 x 1.2
Dependency:
Refer to: p9588
Refer to: C01711
Notice:
Reducing this percentage value can adversely affect actual value sensing with synchronous motors.
If the value is increased, this results in an increased motor power loss.
Note:
This parameter is only effective for encoderless actual value sensing (p9506/p9306 = 1, 3).
For p9783 = maximum value, current injection is deactivated.
Current injection is not effective in the U/f control mode.
Description:
Display to diagnose acceleration values of the encoderless actual values sensing.
Index:
[0] = Setpoint acceleration value
[1] = Actual acceleration value
Dependency:
Refer to: p9589
Note:
For index 0:
Shows the parameterized acceleration value of p9589.
For index 1:
Shows the actually measured acceleration values of the encoderless actual value sensing
Description:
Display to diagnose acceleration values of the encoderless actual values sensing.
Index:
[0] = Setpoint acceleration value
[1] = Actual acceleration value
Dependency:
Refer to: p9589
Note:
For index 0:
Shows the parameterized acceleration value of p9589.
For index 1:
Shows the actually measured acceleration values of the encoderless actual value sensing
p9783
SI Motion act. value sensing sensorless synchr. motor I_inject / Actv sl sync I_inj
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-50.00 [%]
0.00 [%]
-20.00 [%]
r9784[0...1]
SI Motion diagnostics sensorless acceleration / Diag sl a
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [mm/s²]
- [mm/s²]
- [mm/s²]
r9784[0...1]
SI Motion diagnostics sensorless acceleration / Diag sl a
VECTOR_G (Safety
rot)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [rev/s²]
- [rev/s²]
- [rev/s²]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......