4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1868
List Manual (LH2), 07/2016, A5E03263479A
F35003
TM54F: Acknowledgment on the Control Unit is required
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A fault on the Terminal Module 54F (TM54) was acknowledged using the safe acknowledgment (p10006).
An additional acknowledgment is also required at the Control Unit.
Remedy:
- acknowledge all faults on the Control Unit (BI: p2102).
or
- acknowledge all faults on the drive object TM54F (BI: p2103, p2104 or p2105).
Note:
A fault acknowledgment is triggered with a 0/1 signal.
F35004
TM54F: communication cycle invalid
Message value:
Fault cause: %1 bin
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
Terminal Module (TM)
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
- the communication cycle specified in p10000[x] does not correspond with the monitoring cycle of the drive object,
which was specified in p10010[x].
As long as this fault is present, fail safe values are activated in TM54F. All the drives are not enabled.
Fault value (r0949, interpret binary):
If a bit is set in the range bit 0 ... 5, then the following applies:
The communication cycle specified in p10000[x] does not correspond with the monitoring cycle of the drive object
which was specified in p10010[x]. (if only p10000[0] used, then this value must be identical with all monitoring cycles
of the drive objects used in p10010[0..5].)
Bit 0 = 1: p10000[0] does not correspond with the monitoring cycle of p10010[0]
Bit 1 = 1: p10000[1] does not correspond with the monitoring cycle of p10010[1]
..
Bit 5 = 1: p10000[5] does not correspond with the monitoring cycle of p10010[5]
If a bit is set in the range bit 16 ... 21, then the following applies:
Bit 16 = 1: p10000[0] has been selected too low.
Bit 17 = 1: p10000[1] has been selected too low.
..
Bit 21 = 1: p10000[5] has been selected too low.
When using an axis with Basic Safety Functions with TM54F, then the monitoring cycle should be greater than 500us
+ 8 * current controller clock cycles of the drive.
Note:
This error is also signaled if a drive controlled with TM54F is parameterized so that the basic functions are controlled
via TM54F - and simultaneously the extended safety functions or ncSI have been parameterized.
The following applies for fault value = 0:
- since the firmware update of the TM54F it has not been switched off.
- the firmware of the connected TM54F is too old.
See also: p10010 (SI TM54F drive object assignment)
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......