2 Parameters
2.2 List of parameters
SINAMICS G130/G150
202
List Manual (LH2), 07/2016, A5E03263479A
Description:
Displays the encoder status word Gn_ZSW according to PROFIdrive.
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Notice:
Information on Gn_STW/Gn_ZSW can, e.g. be found in the following literature:
SINAMICS S120 Function Manual Drive Functions
Note:
For bit 14:
Displays the acknowledgment for "activate parking encoder" (Gn_STW.14 = 1) or encoder position actual value
(Gn_XIST1) invalid.
For bit 14, 15:
r0481.14 = 1 and r0481.15 = 0 can have one of the following causes:
- the encoder is parked.
- the encoder is deactivated.
- the encoder is being commissioned.
- no parameterized encoder available.
- encoder data set is being changed over.
r0481.14 = 1 and r0481.15 = 1 has the following significance:
An encoder error has occurred and the encoder position actual value (Gn_XIST1) is invalid.
Description:
Displays the encoder status word Gn_ZSW according to PROFIdrive.
r0481[0...2]
CO: Encoder status word Gn_ZSW / Enc Gn_ZSW
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
4010, 4704,
4730, 4750
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Function 1 active
Yes
No
-
01
Function 2 active
Yes
No
-
02
Function 3 active
Yes
No
-
03
Function 4 active
Yes
No
-
04
Value 1
Displayed in r0483
Not present
-
05
Value 2
Displayed in r0483
Not present
-
06
Value 3
Displayed in r0483
Not present
-
07
Value 4
Displayed in r0483
Not present
-
08
Measuring probe 1 deflected
Yes
No
-
09
Measuring probe 2 deflected
Yes
No
-
11
Encoder fault acknowledge active
Yes
No
9676
13
Absolute value cyclically
Displayed in r0483
No
-
14
Parking encoder active
Yes
No
-
15
Encoder fault
Displayed in r0483
None
-
r0481
CO: Encoder status word Gn_ZSW / Enc Gn_ZSW
ENC
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
4704, 4730,
4750
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Function 1 active
Yes
No
-
01
Function 2 active
Yes
No
-
02
Function 3 active
Yes
No
-
03
Function 4 active
Yes
No
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......