SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
841
2 Parameters
2.2 List of parameters
Note:
For value = 99 (automatic) the following applies:
- if a COMM BOARD is not inserted, then the onboard interface (PROFIBUS/PROFINET/USS) communicates via
IF1.
- if a CBE20 is inserted, then the following applies:
-- CU320-2 DP: PROFINET CBE20 communicates via IF1 and PROFIBUS/USS via IF2.
-- CU320-2 PN: PROFINET onboard communicates via IF1 and PROFINET CBE20 via IF2.
- CAN CBC10 always communicates via IF2.
For a value not equal to 99 (automatic) the following applies:
- both indices must be set to a number not equal to 99 (automatic).
A change only becomes effective after POWER ON, reset or download.
Description:
Sets the monitoring time to monitor the process data received via COMM BOARD.
If, during this time, the Control Unit does not receive any process data from the COMM BOARD, then an appropriate
message is output.
Dependency:
Refer to: p8835
Note:
This monitoring function only monitors the connection between the Control Unit and COMM BOARD and not the data
traffic on the fieldbus.
For CBE20 firmware version MODBUS TCP (p8835 =5) then the fieldbus data traffic is also monitored.
Value = 0: Monitoring is deactivated.
Description:
Sets the send configuration data for the COMM BOARD.
The setting is activated with p8842.
Dependency:
Refer to: p8842
Note:
The configuration data are specific to the inserted COMM BOARD.
For CBE20, the configuration data are not relevant.
Description:
Activate a modified send configuration for COMM BOARD.
With p8842 = 1, the values in p8841 are transferred to the COMM BOARD and activated. After this, p8842 is
automatically set to zero.
Dependency:
Refer to: p8841
Note:
For CBE20, certain SINAMICS parameters are newly evaluated and activated. An existing, cyclic bus connection is
interrupted.
p8840
COMM BOARD monitoring time / CB t_monit
CU_G130_PN (COMM
BOARD, PN CBE20),
CU_G150_PN (COMM
BOARD, PN CBE20),
CU_G130_DP (COMM
BOARD, PN CBE20),
CU_G150_DP (COMM
BOARD, PN CBE20)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
65535000 [ms]
20 [ms]
p8841[0...239]
COMM BOARD send configuration data / CB s config_dat
CU_G130_PN (COMM
BOARD, PN CBE20),
CU_G150_PN (COMM
BOARD, PN CBE20),
CU_G130_DP (COMM
BOARD, PN CBE20),
CU_G150_DP (COMM
BOARD, PN CBE20)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 65535
0
p8842
Activate COMM BOARD send configuration / CB s config act
CU_G130_PN (COMM
BOARD, PN CBE20),
CU_G150_PN (COMM
BOARD, PN CBE20),
CU_G130_DP (COMM
BOARD, PN CBE20),
CU_G150_DP (COMM
BOARD, PN CBE20)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
2199, 2200
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......