2 Parameters
2.2 List of parameters
Note:
The interface configuration (p8900 and following) is activated with p8905 = 1.
The parameter is not influenced by setting the factory setting.
Description:
Sets the DHCP mode for the Industrial Ethernet interface (X127) on the Control Unit.
The actual DHCP mode is displayed in parameter r8914.
Value:
0:
DHCP off
2:
DHCP on, identification using MAC address
3:
DHCP on, identification via name of station
Dependency:
Refer to: p8905, r8914
Note:
The interface configuration (p8900 and following) is activated with p8905.
The parameter is not influenced by setting the factory setting.
Description:
Setting to activate the interface configuration for the Industrial Ethernet interface (X127) on the Control Unit.
p8905 is automatically set to 0 at the end of an operation.
Value:
0:
No function
1:
Activate configuration
2:
Activate and save configuration
3:
Delete configuration
Dependency:
Refer to: p8900, p8901, p8902, p8903, p8904
Refer to: A08561
Note:
When a project is downloaded, the interface configuration is only activated if, in the offline project, parameter p8905
is set = 1 or 2.
For p8905 = 1:
The interface configuration (p8900 and following) is activated.
For p8905 = 2:
The interface configuration (p8900 and following) is activated and saved to non-volatile memory.
For p8905 = 3:
The interface configuration is reset to the factory setting at all points.
The factory settings for the interface configuration are loaded on activation (p8905 = 1) or at the next POWER ON.
Description:
Activation of the FTP server.
Permits the FTP access to the /INSTALL/SINAMICS directory of the memory card.
Value:
0:
No
1:
Yes
p8904
IE DHCP mode / IE DHCP mode
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
p8905
IE Interface configuration / IE IF config
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
p8908
Activate FTP / Act FTP
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......