2 Parameters
2.2 List of parameters
SINAMICS G130/G150
638
List Manual (LH2), 07/2016, A5E03263479A
Description:
Setting to acknowledge all active faults of a drive object.
Notice:
Safety messages cannot be acknowledged using this parameter.
Note:
Parameter should be set from 0 to 1 to acknowledge.
After acknowledgment, the parameter is automatically reset to 0.
Description:
Sets the mode to change over the master control / LOCAL mode.
Value:
0:
Change master control for STW1.0 = 0
1:
Change master control in operation
Danger:
When changing the master control in operation, the drive can manifest undesirable behavior - e.g. it can accelerate
up to another setpoint.
Description:
Displays the number of parameters for this drive unit.
The number comprises the device-specific and the drive-specific parameters.
Dependency:
Refer to: r0980, r0981, r0989
Description:
Index 0:
Displays the boot state.
Index 1:
Displays the partial boot state
Value:
0:
Not active
1:
Fatal fault
10:
Fault
20:
Reset all parameters
30:
Drive object modified
40:
Download using commissioning software
p3981
Acknowledge drive object faults / Ackn DO faults
All objects
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
8060
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p3985
Master control mode selection / PcCtrl mode select
VECTOR_G, B_INF
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
r3986
Number of parameters / Param count
All objects
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r3988[0...1]
Boot state / Boot_state
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 10800
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......