SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
269
2 Parameters
2.2 List of parameters
Description:
Sets the signal source to select the Drive Data Set, bit 4 (DDS, bit 4).
Dependency:
Refer to: r0051, r0837
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the freely assignable motor number for the motor changeover.
Dependency:
Refer to: p0827
Notice:
When changing over motor data sets with the same motor number (e.g. star-delta changeover) and for a motor with
brake, the motor brake remains open during the changeover.
Note:
When the motor data sets are changed over, the following applies:
The same motor number signifies the same thermal model.
For the same motor number, the correction values of the Rs, Lh or kT adaptation are applied for the data set
changeover (refer to r1782, r1787, r1797).
Description:
Sets the bit number for every motor data set.
Example:
p0827[0] = 0: For MDS0, r0830.0 is switched.
p0827[1] = 5: For MDS1, r0830.5 is switched.
Dependency:
Refer to: p0826, r0830
Note:
A motor is only changed over (a new motor selected) after the pulses have been suppressed.
When the motor data sets are changed over, the following applies:
Bit numbers that are not identical, signify that the motor must be changed over.
p0824[0...n]
BI: Drive Data Set selection DDS bit 4 / DDS select., bit 4
VECTOR_G
Can be changed:
C2(15), T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
8565, 8575
P-Group:
Data sets
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p0826[0...n]
Motor changeover motor number / Mot_chng mot No.
VECTOR_G
Can be changed:
C2(3)
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
MDS, p0130
Func. diagram:
8575
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 15
0
p0827[0...n]
Motor changeover status word bit number / Mot_chg ZSW bitNo.
VECTOR_G
Can be changed:
C2(3)
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
MDS, p0130
Func. diagram:
8575
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 15
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......