SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
179
2 Parameters
2.2 List of parameters
Description:
Sets the extended configuration of the Sensor Module.
Dependency:
Refer to: p0430, r0459
Note:
A value of zero is displayed if an encoder is not present.
For bit 00:
When the data logger (trace) is activated, in the case of a fault, data before and after the event are recorded (traced)
and saved in files on the non-volatile memory medium. Experts can then evaluate this data.
For bit 01:
If bit = 0, the zero mark is evaluated by ANDing tracks A and B and the zero mark.
For bit = 1, the zero mark is evaluated depending on the direction detected. For a positive direction, the positive edge
of the zero mark is considered and for a negative direction, the negative edge of the zero mark.
For bit 02:
If the bit is set, in the event of a deviation less than the tolerance window for the zero mark (p4681, p4682), the
pulses per revolution are corrected. If the bit is not set, encoder fault F3x131 is triggered.
For bits 05, 04:
Bit 5/4 = 0/0: Signal evaluation per period, 4x.
Bit 5/4 = 1/0: Signal evaluation per period, 4x.
Bit 5/4 = 0/1: Signal evaluation per period, 1x.
Bit 5/4 = 1/1: Illegal setting.
For bit 06:
If the function is active, when dn/dt monitoring responds, the velocity actual value is internally frozen for a time
equivalent to two current controller sampling times. The rotor position continues to be integrated. The actual value is
then re-enabled after this time has expired.
For bit 07:
When the bit is not set, the incorrect pulses that have occurred up until now are accumulated in p4688.
When the bit is not set, p4688 indicates the incorrect pulses that have still not been corrected.
p0437[0...n]
Sensor Module configuration extended / SM config ext
ENC (Lin_enc)
Can be changed:
C2(4)
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-
-
0011 0000 0000 0000 0000
1000 0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Data logger
Yes
No
-
01
Zero mark edge detection
Yes
No
-
02
Correction position actual value XIST1
Yes
No
-
04
Edge evaluation bit 0
Yes
No
-
05
Edge evaluation bit 1
Yes
No
-
06
Freeze the speed actual value for dn/dt
errors
Yes
No
-
07
Do not accumulate the number of incorrect
pulses
Yes
No
-
11
Fault handling after PROFIdrive
Yes
No
-
12
Activate additional messages
Yes
No
-
13
Support absolute position for incremental
encoder
Yes
No
4750
25
Deselect monitoring multiturn
representation in Gx_XIST2
Yes
No
-
26
Deselect track monitoring
Yes
No
-
28
EnDat linear encoder monitoring
incremental/absolute
Yes
No
-
29
EnDat encoder initialization with high
accuracy
Yes
No
-
31
Analog unipolar track monitoring
Yes
No
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......