2 Parameters
2.2 List of parameters
SINAMICS G130/G150
948
List Manual (LH2), 07/2016, A5E03263479A
Dependency:
Refer to: C01711
Note:
For a linear axis, the tolerance is internally limited to 10 mm.
For a "linear axis with rotating motor" and factory setting of p9520, p9521 and p9522, the factory setting of p9542
corresponds to a position tolerance of 36 ° on the motor side.
Description:
Sets the tolerance for the crosswise data comparison of the actual position between the two monitoring channels.
For encoderless motion monitoring functions, the tolerance must be set to a higher value (12 degrees rotary, 1 mm
linear).
Dependency:
Refer to: C01711
Description:
Sets the factor to increase the tolerance for the crosswise data comparison of the actual position between the two
monitoring channels while the gearbox stage is being switched over.
This factor is effective when actual value synchronization is activated and when deactivated.
Depending on the following tolerance, the following is obtained:
- actual value synchronization activated: p9549 * p9543
- actual value synchronization deactivated: p9542 * p9543
Description:
Sets the tolerance for checking the actual values.
For an incremental encoder, the actual values are checked after referencing; for an absolute encoder, when
switching on.
Dependency:
Refer to: C01711
Note:
A change only becomes effective after a POWER ON.
For linear axes, the maximum value is limited to 1 mm.
p9542
SI Motion act val comparison tol (crosswise) (Control Unit) / SI Mtn act tol CU
VECTOR_G (Safety
rot)
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0010 [°]
360.0000 [°]
0.1000 [°]
p9543
SI Motion gearbox switching position tolerance factor (CU) / SI Mtn grbx tol CU
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 1000
1
p9544
SI Motion actual value comparison tolerance (referencing) (CU) / SI Mtn ref tol
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0000 [mm]
36.0000 [mm]
0.0100 [mm]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......