2 Parameters
2.2 List of parameters
SINAMICS G130/G150
552
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency:
Refer to: r2197, r2198, r2199
Description:
Sets the time constant of the PT1 element to smooth the speed / velocity actual value.
The smoothed actual speed/velocity is compared with the threshold values and is only used for messages and
signals.
Dependency:
Refer to: r2169
Description:
Sets the signal source for speed setpoint 2.
The sum of p2151 and p2154 is used for the following messages/signals:
"Speed setpoint - actual value deviation within tolerance t_off" (r2197.7)
"Speed setpoint - actual value deviation within tolerance t_on" (r2199.4)
"Ramp-up/ramp-down completed" (r2199.5)
Dependency:
Refer to: p2151, r2197, r2199
Description:
Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
p2151[0...n]
CI: Speed setpoint for messages/signals / n_set for msg
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
8011
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- -
1170[0]
p2153[0...n]
Speed actual value filter time constant / n_act_filt T
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
1000000 [ms]
0 [ms]
p2154[0...n]
CI: Speed setpoint 2 / n_set 2
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
8010
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- -
0
p2155[0...n]
Speed threshold 2 / n_thresh val 2
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
900.00 [rpm]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......