SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
309
2 Parameters
2.2 List of parameters
Description:
Setting and connector output for fixed speed setpoint 12.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Setting and connector output for fixed speed setpoint 13.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Setting and connector output for fixed speed setpoint 14.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Setting and connector output for fixed speed setpoint 15.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1012[0...n]
CO: Fixed speed setpoint 12 / n_set_fixed 12
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3010
P-Group:
Setpoints
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1013[0...n]
CO: Fixed speed setpoint 13 / n_set_fixed 13
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3010
P-Group:
Setpoints
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1014[0...n]
CO: Fixed speed setpoint 14 / n_set_fixed 14
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3010
P-Group:
Setpoints
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1015[0...n]
CO: Fixed speed setpoint 15 / n_set_fixed 15
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3010
P-Group:
Setpoints
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......